Temperature sensor THERMOCONT® TK4SS

Delivery Time: not specified

Compact temperature sensor with Pt platinum resistance sensor

  • Measuring ranges from -50 to +200 °C (-58 to +392 °F)
  • Long-term stable temperature sensor made of platinum
  • Extremely short response times < 2s
  • Slim design – diameter 12mm
  • Fully welded stainless steel housing
  • High protection class IP69K/IP67
  • High accuracy ≤ ±0,2K
  • Electronics from 4 to 20mA FSK / RS485/IO-Link
  • Authorization ATEX/IECEx

Description

The THERMOCONT® TK4 is a universally applicable temperature sensor and is particularly suitable for demanding and time-critical measuring tasks, especially in confined installation situations and high temperature loads.

Measuring media are gases, vapors, liquids and dusts.

The process temperature acts on a directly contacted thin-film platinum sensor element via the sensor tube. It causes a change in resistance there, which is converted into a corresponding output signal by the optional transmitter electronics.

Ausführung Standard
Sensor Widerstandssensor Pt-Platin – IEC 60751
Zulassung Standard
Prozessanschluss ohne Prozessanschluss
Gewinde ISO 228-1 – G¼“A
Gewinde ISO 228-1 – G½“A
Gewinde ANSI – NPT ¼“
Gewinde ANSI – NPT ½“
Gewinde ISO 228-1 – G ½“A, O-Ring frontbündig, PN40
Gewinde ISO 228-1 – G ½“A, metallisch dichtend, PN40
Milchrohrverschraubung DIN 11851 – DN25, PN40
Clamp DIN 32676 – DN25…40/1”…1½“, ISO 2852 – DN25…38, PN25
Varivent F – DN25…32 (1…1¼”), Ø 50mm, PN40
Werkstoff Prozessdichtung ohne
FKM/FPM – FDA
EPDM – FDA
Werkstoff Prozessanschluss CrNi-Stahl
Werkstoff Anschlussgehäuse CrNi-Stahl
Messbereich Temperatur Pt Klasse A – IEC 60751
0°C…+50°C (+32°F…+122°F)
0°C…+100°C (+32°F…+212°F
0°C…+150°C (+32°F…+302°F)
0°C…+200°C (+32°F…+392°F)
-50°C…+50°C (-58°F…+122°F)
-50°C…+100°C (-58°F…+212°F)
-50°C…+150°C (-58°F…+302°F)
-50°C…+200°C (-58°F…+392°F)
Elektronik – Ausgang Pt100 Klasse A – IEC 60751, 4-Leiter
Pt1000 Klasse A – IEC 60751, 4-Leiter
Strom 4…20mA, FSK-Schnittstelle, 2-Leiter
RS485 Modbus-RTU, 4-Leiter
IO-Link, Strom 0/4…20mA / 2x Sout PP, 4-Leiter
Elektronik – Funktion Standard
Halsrohr ohne
35mm
Länge L2
Fühlerrohr – Durchmesser Ø6mm
Messgenauigkeit Pt Klasse A – IEC 60751
≤ ±0,25K + 0,002 ∗ T 
Xcellence ≤ ±0,15K, Linearitätsprotokoll
Elektrischer Anschluss Stecker M12x1 A
Länge L1 – Fühlerrohr 30mm
50mm
100mm
150mm
200mm
mm (≤ 300mm)
Länge L2 – Halsrohr mm (050…200mm)

Dokumentation deutsch

Bedienungsanleitung
Datenblatt

Dokumentation englisch

Bedienungsanleitung
Datenblatt

Product configurator