Ultra sonic fill level sensor Sonicont USD 150

for contactless continuous fill level measurement in liquids and solid materials


Technical Data

Measuring range
Liquids
: 15 m
Solids: 7 m

Blocking distance: 0.6 m
Deviation: ± 4 mm, or 0.2% of set measuring range (greater)
Resolution: 2 mm
Frequency: 35 kHz
Pulse: dep. the type of sensor (max. 0.5 Hz at 2 Hz 2-wire/max at 4-wire)
Min reaction time: 0.5 s at 4-wire, 2 s for 2-wire
3dB beam angle: 6°
Output: 4 .. 20 mA with HART protocol (standard), PROFIBUS PA, FOUNDATION Fieldbus (option)
Load: For HART communication minimum of 250 ohms
Installation: Perpendicular to the product surface
Ambient temperature: -40 ... +80°C
Protection: IP68, IP20 with open cover
Process temperature: -40 ... +80°C
Pabs process pressure: 0.7 ... 2,5 bar
Power supply: two wire: 14-36V DC, four-wire: 10.5-32V DC, 90-253 V AC 50/60 Hz
CE-mark: Prosonic meets the legal requirements of the EC directives.
Ex approvals: ATEX II ½ G, 2G EEx ia IIC T6, EEx d (ia) IIC T6, ATEX II ½ D, 1/3D, ATEX II 3G EEx nA II T6, ATEX II ½ D, 1/3D