Precont® HE5409

Delivery Time: not specified

cost-effective differential pressure transmitter with hose connection for wall mounting, in two-wire technology

  • Inexpensive differential pressure transmitter
  • Compact design
  • Easy handling

 

Categories: ,

Description

The differential pressure transmitter is a transmitter Precont® HE5409 for small and medium pressures. Due to the layout with different pressure sensors measuring ranges between 0 and 2,5 mbar, 0 and 5 mbar, 0 and 10 mbar, 0 and 25 can mbar, 0 to 50 mbar and performed 0 to 100 mbar. Two connecting cables are used for power supply. The supply current is the measurement signal of 4 … 20 mA. The state is indicated by an LED.

Low_Cost 4_20mA_2_Draht 100_g_l Bauform_kompakt Montage_einfach
Messbereich 0mbar…+1000mbar (typabhängig)
Max. Differenzdruck 750mbar
Max.Differenzdruck
(gegen Umgebung)
1000mbar
Medium Luft
Trockene, nicht aggressive Gase
Grundgenauigkeit ±1% vom Endwert
Temperaturdrift ±0,05%/K vom Endwert
Hysterese ±0,5% vom Endwert
Messsystem Halbleitersensor
Hilfsenergie Ub = 10 V…36 V DC
Analogausgang 4…20mA, 2-Leiter
Max. zuläsige Bürde RA ≤ (Ub – 9V) / 0,02A
Druckanschluss Schott-Steckverschraubungen für 6mm Schlauch-Außendurchmesser
Gehäuse Staubdichtes Polycarbonatgehäuse
Abmessung 113 x 80 x 60 (B x H x T)
Schutzart IP65
Montage Wandmontage
Einbaulage senkrecht
Anschluss Federkraftklemmen
Kabelverschraubung 1 x M16 x 1,5N für Kabeldurchmesser von 4mm…8mm

Documentation german

Datasheet

Documentation english

Datasheet

Product configurator