Hydrocont (Ex)S50

Delivery Time: not specified

Hydrostatic filling level measurement, suitable also for Ex areas

With dry capacitive measurement system and with display, 4-20mA or 0-10V output and 2 pnp switching outputs

  • Hygene applications
  • Precise ceramic cell
  • Bright LED ensures exclent reading

 

Description

The devices of the series Hydrocont® S50 with integrated digital evaluation electronic are compact sensors for measuring and monitoring of fill levels.

The excellent characteristics like highest strength against pressure and pressure blows, high resistance against chemicals and corrosion, very good insensitiveness against temperature shocks and EM interference, highest accuracy and long term stability and also low influence of temperature makes it possible to use the sensor in all pressureless containers for liquid medium like water, waste water, solvents, oil, sludge, grease, cleaning agents, etc.

The level measurement system Hydrocont® S50 is built in the wall of the medium container. The medium contacts directly the ceramic membrane of the sensor without using a pressure mediator liquid and causes there a deflection of the membrane because of the hydrostatic pressure of the medium.

At the maximum deflection the membrane contacts a robust ceramic carrier and because of this, the membrane come through over pressure of e.g. 80-times of nominal load at a sensor with a pressure range of 0…50 mbar without damage. The fill level proportional pressure signal of the ceramic membrane is recorded from a processor with high resolution, adjusted according to the settings and converted into a high resolution output signal of 4…20mA or 0…10V. By using 3 keys and an LED display the sensor measurement range, the display, the PNP-switching outputs and the damping can be adjusted or the behaviour in the case of failure and the release of the fast adjustment can be set.

 

 

Function

The level measurement system Hydrocont® S50 is built in the wall of the medium container.
The medium contacts directly the ceramic membrane of the sensor without using a pressure mediator liquid and causes there a deflection of the membrane because of the hydrostatic pressure of the medium.
At the maximum deflection the membrane contacts a robust ceramic carrier and because of this, the membrane come through over pressure of e.g. 80-times of nominal load at a sensor with a pressure range of 0…50 mbar without damage.
The fill level proportional pressure signal of the ceramic membrane is recorded from a processor with high resolution, adjusted according to the settings and converted into a high resolution output signal of 4…20mA or 0…10V.

By using 3 keys and an LED display the sensor measurement range, the display, the PNP-switching outputs and the damping can be adjusted or the behaviour in the case of failure and the release of the fast adjustment can be set.
The switching state of the two PNP-switching output is signalled by one LED for every output.

4_20mA_2_PNP Ueberlast_80 Ex_Zulassung LED_Anzeige 4_20mA_2_PNP
Auxiliary power
Output variations A/B/C/D 4..20 mA, 2-wire, Profibus PA
Output variations E/F/G/H 0…10 V, 3-wire
Permitted supply voltage
Variation C/D 10,5 V up to 45 V DC
Variation A/B/E/F/G/H 14,5 V up to 45 V DC
Residual ripple ≤ 2 Vss
Switching outputs (S1 / S2) 2x PNP-switching on +VS
Output current > 250 mA,current limited, short circuit predected
Output delay with damping 1 T90 typ. 260 ms, max. 310 ms
Damping adjustment range 0,3…30 Sec / 100 Steps
Measuring accuracy
Temperature deviation ≤ 0,1% / 10 K of the nominal range
Deviation in characteristics ≤ 0,1% / 0,2% of the nominal range
Calibration deviation ≤ 0,05% of the nominal range
Long term drift ≤ 0,1% / year of the nominal range
Influence of supply voltage ≤ 0,02% / 10 V of the nominal range
Resolution better 1 µA resp. 0,5 mV (16 Bit = 65536 Steps)
Materials
Membrane Ceramic AL2O3 96%
Ceramic High purity AL2O3 99,9%
Prozessanschluss Steel 1.4404 / others on request
Temperature separator Steel 1.4404 / others on request
Gaskets  Viton® / EPDM / Neopren® / Perfluorelastomer
Connection housing Steel 1.4301 / PUM – Delrin® / PBT
Extension cable PE/FEP
Environmental conditions
Medium temperature -40°C…+125°C (for 1h 140°C);
with extension cable -20°C…+70°C
Ambient / storage temperature -40°C…+85°C;
with extension cable -20°C…+70°C
Protection class IP65/IP67

Documentation english

User manual
Datasheet

Software

Profibus GSD

Product configurator