Precont® D40

0,00

Delivery Time: not specified

With flush, capacitive ceramic membrane for food applications

  • To operate under extreme climatic conditions
  • On-site programmable with bright LED
  • Analouge and up to 4 switching points

 

Description

The Precont® D40 is used in all fields of proceeding and process technique.
The excellent characteristics like pressure strength, high chemical resistance, corrosion protection and insensitivity against temperature shocks allows the use in the hardest applications for the measurement of gases, steams and liquids.

By the special contruction the device is especially suitable for the use in areas witht hight air humidity and at condensed water formation where conventional devices can not or can only be used with an expensive placed air compensation capillary.

4_20mA_2_PNP Feuchteresistent Messzelle_kapazitiv LED_Anzeige 4_20mA_2_PNP Ex_Zulassung
Auxiliary power supply
output signal 4…20mA
(with display)
16,5 V…45 V DC
16,5 V…30 V DC (with Ex variant)
output signal 4…20mA
(with display)
12,5 V…45 V DC
12,5 V…30 V DC (with Ex variant)
output signal 0…10V 16,5 V…45 V DC
16,5 V…30 V DC (with Ex variant)
Supply current
2-wire 4…20mA ≤ 22mA (PNP-switching outputs in neutral)
3-wire 0…10V ≤ 10mA (PNP-switching outputs in neutral)
2xPNP-switching output
Function PNP-switching on +Vs
Output current ≤ 250mA
current limited
short circuit protected
Measurement accuracy
Characteristics deviation ≤ ±0,1% / ±0,2% FS
Measuring range 0,2bar/0,4bar/0,6bar: ±0,35% FS
Long term drift ≤ ±0,1% FS / year not cumulative
Temperature deviation ≤ ±0,30% FS / 10 K (Zero / Span)
Materials
Membrane
(medium contact)
Ceramics AL2O3 99,9%
Process connection
(medium contact)
Steel 1.4404/316L resp. 1.4571/316Ti
Connection housing CrNi-Steel
Gaskets
(medium contact)
FPM – fluoroelastomer (Viton®)
EPDM – ethylene-propylene-diene monomer
CR – chloroprene rubber (Neopren®)
FFKM – perfluorelastomere (Kalrez®)
NBR – nitrile-butadiene rubber
Environmental conditions
Ambient temperature -40°C…+85°C
Process temperatures – 40°C…+125°C
Process pressure ranges -1bar … +16bar
Turn-Down 4:1
Schutzart IP65 / IP67 (EN/IEC 60529)

Documentation german

User manual
Datasheet

Documentation english

User manual

Product configurator