Hydrocont B

Delivery Time: not specified

Level sensor for water and waste water Ø 40mm

4-20 mA – output, optional temperature measurement Pt100, dry capacitive measurement system + over voltage protection

  • Solid sensor, ideal for waste water applications
  • Special cable with double isolation – no penetration of liquids in case of external damage
  • Overvoltage protection integradet in the probe

 

Description

The device Hydrocont® B with integrated analogue evaluation electronic is a compact sensor for continuous measurement of fill levels in liquid media.
This includes e.g. the registration of levels in reservoirs, clarification basins, deep wells etc., but also the fill level measurement in closed containers.
For applications, where food or drink water suitability is necessary, a corresponding put in variant can be ordered.

The excellent characteristics like highest strength against pressure and pressure blows, high resistance against chemicals and corrosion, very good insensitiveness against temperature shocks and EM interference, highest accuracy and long term stability and also low influence of temperature makes it possible to use the sensor in all containers for liquid medium like water, waste water, solvents, oil, sludge, grease, cleaning agents, etc. In addition to the level measurement the temperature of the medium can be measured by a Pt100 resistor, that is integrated in the sensor.

 

Function

The sensor of the fill level measurement system Hydrocont® B is sunken down into the medium by the carrying cable and a suitable fastening, e.g. cable clamp fixing, screw plug or connection housing with process connection. The sensor can be alternatively directly mounted into the wall of the medium container by using a corresponding process connection.

The medium contacts directly the ceramic membrane of the sensor without using a pressure mediator liquid and causes there a deflection of the membrane because of the hydrostatic pressure of the medium.

At the maximum deflection the membrane contacts a robust ceramic carrier and because of this, the membrane come through over pressure of e.g. 40-times of nominal load at a sensor with a pressure range of 0…100 mbar without damage. The fill level proportional pressure signal of the ceramic membrane is measured by the integrated analogue electronic and converted into a output current signal of 4…20mA or into a pulse frequency modulated current signal (PFM) of 90-520 Hz.

The measurement signal range is fix adjusted by factory and cannot be adjusted by the customer. Because of this there are many different standard measurement ranges available. Additionally to this, the factory provided adjustment can be carried out by customer specification.

The output signal can be provided with an optional damping, e.g. to compensate wave movements due to mixing machines. To include the damping in the sensor, make a special note in the order.

Optionally a temperature dependent resistor Pt-100 in 3-wire-technic can be integrated in the sensor. By using this temperature measurement resistor a temperature measurement of the fill medium with removing the lead resistance can be realized in parallel. When using a wall housing a Pt-100 transmitter that is adjusted by customer specification can be integrated in this housing.

The sensor of the fill level measurement system Hydrocont® B can furthermore equipped with an integrated over voltage protection, that protects the measuring system from destruction by e.g. atmospheric influences.

Ueberlast_40 Temperaturmessung_integriert 4_20mA_2_Draht Blitzschutz Genauigkeit_0_1 Ex_Zulassung
Auxiliary power
Output 4..20 mA, 2-wire
Permitted supply voltage
Standard-Variante 11,5 V up to 45 V DC
Ex-Variante 11,5 V up to 30 V DC
Ripple ≤ 2 Vss
Delay time output T90 < 100µs
Allowable product temperature -20°C…+70°C
Overvoltage protection
Surge Protection 30V (Peak value; against earth)
Nominal discharge current 2 500A (wave 8/20µS)
Accuracy
Temperature deviation ≤ 0,1% / 10 K of the nominal measurement range
Kennlinienabweichung ≤ 0,1% / 0,2% of the nominal measurement range
Calibration deviation ≤ 0,05% of the nominal measurement range
Long term drift ≤ 0,1% / year of the nominal measurement range
Supply voltage influence ≤ 0,02% / 10V of the nominal measurement range
Resolution infinite, because analog measurement electronics
Materials
Membrane Ceramic AL2O3 96%
Ceramic High Purity AL2O3 99,9%
Slopes sensor Steel 1.4404
Cap Steel 1.4404
Sealing FPM (Viton®) / EPDM / Neopren® / Kalrez®
Connection housing Polyacetal POM (Delrin)
screw made of Stahl 1.4404
Carrying cable PE/FEP
Wall mounted housing PC / PS
Protection class
Slopes sensor IP68
Sealing screw / Connection housing IP67
Wall mounted housing IP65

Documentation english

User manual
Datasheet

Product configurator

    inkl. Prozessanschluss, Maß in mm