Vibrocont SCM-300

Delivery Time: not specified

Vibration level limit switch for liquids

Miniaturized small vibration fork
Screw-in thread G½” und G¾”

  • Usable for all liquids and pastes
  • WHG approval
  • Short oscillator

 

Categories: , , Tag:

Description

Vibrocont SCM-300 is a point level switch for liquids. The Vibrocont SCM-300 is designed for industrial applications in all industries, mainly the machinery industry. The Vibrocont SCM-300 is used for overfill prevention or pump dry-run protection in cleaning and filter systems as well as in cooling and lubrication vessels.

Compact:
– Smallest vibronic sensor
Safe:
– Continuous self-monitoring
– Reliable switching independent of media properties
Easy:
– No calibration or adjustment
– Plug & play

Field of application

Point level switch in compact design with stainless steel housing.

Process connections: Threads
Temperature: -40 to +150°C (-40 to +302°F)
Pressure: -1 to +40bar (-14.5 to 580psi)
Surface roughness: 3.2µm
Approvals: WHG overfill prevention and leakage detection, CSA C/US, 3.1 material certificate, marine approval, final inspection report

WHG_Zulassung Druck_bis_40 Korresionsbestaendig Bauform_kompakt
DC-PNP-variant
Supply voltage 10 V…30 V DC, 3-wire
Switching capacity 200mA
Power consumption ≤ 15mA
Plug Plug M12
Valve connector
AC/DC-variant
Supply voltage 20 V…253 V AC/DC, 2-wire
Switching capacity 250mA
Power consumption ≤ 3,8mA (at the moment of switch-off < 1mA for 100ms)
Plug Valve connector
Output gerneral
Switching time approx. 0.5 s when covering
approx. 1s when becoming free
Hysteresis max. 3mm
Process connections thread ISO 228 G½”
thread ISO 228 G¾”
thread ISO 228 G1″
EN10226 R½”
EN10226 R¾”
EN10226 R1″
Conditions of use
Mounting position Any
Switching point 13mm with vertical installation (Water +25°C / +1bar)
10,5mm with horizontal installation (Water +25°C / +1bar)
Pipe extension 103mm
Surface roughness Ra ≤ 3,2µm
Ambient temperature -40°C…+70°C
Medium temperature -40°C…+150°C
Operating pressure -1bar … +40bar
Storage temperature -40°C…+85°C
Climate class DIN EN 60068-2-38/IEC 68-2-38
exam Z/AD
Medium density > 0,7 g/cm³
> 0,5 g/cm³
Medium viscosity 1mPas … 10000mPas
Dynamic viscosity
Protection class IP65/67 (with plug variant M12)
IP65 (with valve plug variant)
Approvals
WHG Z-65.11-531
Leak detection system Z-65.40-532

Documentation german

User manual
Datasheet

Documentation english

User manual
Datasheet

Product configurator