Isolation amplifier with sensor supply for the connection of 4…20mA signals out of the explosive hazardous areas
- Safe supply in the ATEX area
- HART signals can be transmitted
- 3x galvanic isolated
Description
MAIN FEATURES
- Auxiliary power, wide-range power supply, flexible voltage supply
- Bidirectional HART® transmission
- HART® communication sockets for sensor parameterisation
- Compact side-by-side housing
- Sensor power supply for 4…20mA devices
- Compact DIN rail housing 22.5mm
- 20…253 V AC/DC wide-range power supply
- Suitable for connection of intrinsically safe devices Ex Zone 2 [ec]
APPLICATION
- Galvanic isolation of 4…20 mA circuits
- Elimination of ground loops
- Power supply for 2-wire transducers
The active barrier is used for the transmission and galvanic isolation of 0/4 to 20 mA/ HART signals. The device has an active/passive current input to which a 2- or 4-wire transmitter can be directly connected. The output of the device can be operated actively or passively. The current signal is then available to the PLC / controller or to other instrumentation at plug-in screw terminals or optional push-in terminals.
HART communication signals are transmitted bidirectionally by the device. Connection sockets for connecting HART communicators are integrated into the front of the device.
The device is optionally available as an „associated apparatus“, which allows devices to be connected in Ex Zone 0/20 [ia] and operated in Ex Zone 2 [ec]. 2-wire transmitters are supplied with power, and transmit analog 0/4 to 20 mA/HART measured values from the hazardous area to the non-hazardous area.
Bauform: Breite x Länge x Höhe (mit Anschlussklemmen): 17,5 x 116 x 107,5 mm
Eingang: 4…20 mA eigensicher
Betriebsspannung:24…230 V AC/DC; HART durchlässig
Ausgang: 4…20 mA, aktiv
Zertifizierung: ATEX, IECEx: II(1)G [Ex ia Ga] IIC / ATEX, IECEx: II(1)D [Ex ia Da] IIIC / ATEX: II(3)G [Ex ec Gc] IIC